M215 Installation and Operation
2014 Enphase Energy Inc. All rights reserved. 141-00012 Rev 06
11
Grounding Considerations
With the M215-60-2LL-S22-IG, S23-IG, or S24-IG, the DC circuit within the M215 is isolated and insulated
from ground. Ground fault protection (GFP) is integrated into the microinverter. Because of this, the
M215-60-2LL-S22-IG, S23-IG, and S24-IG do not require a GEC. As a result, they take less time to install
than other microinverters, save money, and increase safety.
If you are installing the M215-60-2LL-S22, S23, or S24, a GEC or other compliant grounding method is
required.
TIP: If installing a mix of IG (Integrated Ground) and non-IG microinverters, install the
non-IG microinverters closer (electrically) to the junction box to minimize GEC use.
Utility Service Requirements
The M215 Microinverter works with split phase 240 VAC service or with three phase 208 VAC service.
Measure AC line voltage at the electrical utility connection to confirm that it is within the ranges shown:
240 Volt AC, Split Phase
L1 to L2
211 to 264 VAC
L1 to L2 to L3
183 to 229 VAC
L1, L2 to neutral
106 to 132 VAC
L1, L2, L3 to neutral
106 to 132 VAC
Branch Circuit Capacity
Plan your AC branch circuits to meet the following limits for maximum number of M215s per branch when
protected with a 20-amp over-current protection device (OCPD).
Maximum number of M215s when protected with a 20 A OCPD
Service type
Max M215s per AC branch circuit
Split phase 240 VAC
17
Three phase 208 VAC
25
Lightning and Surge Suppression
Enphase Microinverters have integral surge protection, greater than most traditional inverters. However, if
the surge has sufficient energy, the protection built into the microinverter can be exceeded, and the
equipment can be damaged. For this reason, Enphase recommends that you protect your system with
lightning and/or surge suppression devices (see table). In addition to having some level of surge
suppression, it is also important to have insurance that protects against lightning and electrical surges.
Residential
Commercial
Citel DS72-RS-120 surge protector; data sheet
Delta LA-302 lightning arrestor; website
Leviton 51110 or 51110-001; whole house surge protection
panel; website
Midnight solar surge protection device MNSPD-300 or
MNSPD-300FM (with flush mount box); website
Citel DS73-RS-G surge protector; data sheet
Delta LA-303 lightning arrestor; website
NOTE: Protection against lightning and resulting voltage surge must be in accordance
with local standards.